Public Safety, Fire Marshal R710-6 Liquefied Petroleum Gas Rules
|
|
NOTICE OF PROPOSED RULE |
|
|
DAR File No.: 27573
|
|
RULE ANALYSIS |
|
Purpose of the rule or reason for the change: |
|
|
The Utah Liquefied Petroleum Gas (LPG) Board met in a regularly scheduled Board meeting on November 19, 2004, and proposed that the LPG rule be amended. The purpose of the rule amendment is to update an incorporated reference, update reference sections to correspond to the incorporated reference, and modify the requirement for vehicular guard post installations.
|
|
Summary of the rule or change: |
|
|
The Utah LPG Board proposes to amend Rule R710-6 as follows: 1) in Subsection R710-6-1(1.1), the Board proposes to update an incorporated reference by replacing the 2001 edition of National Fire Protection Association (NFPA) 58 with the 2004 edition of NFPA 58; 2) in Section R710-6-8, the Board proposes to make several numerical and grammatical changes to the section references to make the rule sections correspond with the newly adopted incorporated reference; and, 3) in Subsection R710-6-8(8.6.6), the Board proposes to reword the section with regard to how metal vehicular guard posts are installed.
|
|
State statutory or constitutional authorization for this rule: |
|
|
Section 53-7-305
|
|
| This rule or change incorporates by reference the following material: | |
|
National Fire Protection Association (NFPA), Standard 58, LP Gas Code, 2004 edition
|
|
Anticipated cost or savings to: |
|
the state budget: |
|
|
There would be an anticipated cost to the state budget of approximately $30 per volume to purchase the 2004 edition of NFPA 58. There would be an aggregate anticipated cost to the state budget of approximately $300 to purchase the needed volumes of the 2004 edition of NFPA 58.
|
|
local governments: |
|
|
There would be an anticipated cost to local government of approximately $30 per volume to purchase the 2004 edition of NFPA 58. The aggregate anticipated cost to local government is impossible to anticipate due to the unknown number of volumes of the 2004 edition of NFPA 58 that would be purchased by local government.
|
|
other persons: |
|
|
There would be an anticipated cost to other persons of approximately $30 per volume to purchase the 2004 edition of NFPA 58. The aggregate anticipated cost to other persons is impossible to anticipate due to the unknown number of volumes of the 2004 edition of NFPA 58 that would be purchased by those in the industry and other interested citizens.
|
|
Compliance costs for affected persons: |
|
|
There would be a compliance cost of approximately $30 per volume to purchase the 2004 edition of NFPA 58.
|
|
Comments by the department head on the fiscal impact the rule may have on businesses: |
|
|
There is a fiscal impact on businesses to purchase the 2004 edition of NFPA 58 of only $30 per volume. The industry likes to use the most current edition of the NFPA standards with regard to safety in the usage and handling of LP Gas in the State of Utah.
|
|
The full text of this rule may be inspected, during regular business hours, at the Division of Administrative Rules, or at: |
|
|
Public Safety Fire Marshal 5272 S COLLEGE DR MURRAY UT 84123-2611
|
|
Direct questions regarding this rule to: |
|
|
Brent Halladay at the above address, by phone at 801-284-6352, by FAX at 801-284-6351, or by Internet E-mail at bhallada@utah.gov
|
|
Interested persons may present their views on this rule by submitting written comments to the address above no later than 5:00 p.m. on: |
|
|
01/14/2005
|
|
This rule may become effective on: |
|
|
01/15/2005
|
|
Authorized by: |
|
|
Gary A. Wise, State Fire Marshal
|
|
RULE TEXT |
|
|
R710. Public Safety, Fire Marshal. R710-6. Liquefied Petroleum Gas Rules. R710-6-1. Adoption, Title, Purpose and Scope. Pursuant to Title 53, Chapter 7, Section 305, Utah State Code Annotated 1953, the Liquefied Petroleum Gas (LPG) Board adopts minimum rules to provide regulation to those who distribute, transfer, dispense or install LP Gas and/or its appliances in the State of Utah. There is adopted as part of these rules the following codes which are incorporated by reference: 1.1 National Fire Protection Association (NFPA),
Standard 58, LP Gas Code, [ 1.2 National Fire Protection Association (NFPA), Standard 54, National Fuel Gas Code, 2002 edition, except as amended by provisions listed in R710-6-8, et seq. 1.3 National Fire Protection Association (NFPA), Standard 1192, Standard on Recreational Vehicles, 2002 Edition, except as amended by provisions listed in R710-6-8, et seq. 1.4 International Fire Code (IFC), Chapter 38, 2003 edition, as published by the International Code Council, Inc. (ICC), except as amended by provisions listed in R710-6-8, et seq. 1.5 A copy of the above codes are on file with the Division of Administrative Rules, and the State Fire Marshal's Office. The definitions contained in the afore referenced codes shall also pertain to these rules. 1.6 Title. These rules shall be known as "Rules Governing LPG Operations in the State of Utah" and may be cited as such, and will be hereinafter referred to as "these rules". 1.7 Validity. If any article, section, subsection, sentence, clause, or phrase, of these rules is, for any reason, held to be unconstitutional, contrary to statute, or exceeding the authority of the LPG Board such decision shall not affect the validity of the remaining portion of these rules. 1.8 Conflicts. In the event where separate requirements pertain to the same situation in the same code, or between different codes or standards as adopted, the more restrictive requirement shall govern, as determined by the enforcing authority.
R710-6-8. Amendments and Additions. The following amendments and additions are hereby adopted by the Board: 8.1 All LP Gas facilities that are located in a public place shall be inspected by a certified LP Gas serviceman every five (5) years for leaks in all buried piping as follows: 8.1.1 All buried piping shall be pressure tested and inspected for leaks as set forth in NFPA Standard 54, Sections 4.1.1 through 4.3.4. 8.1.2 If a leak is detected and repaired, the buried piping shall again be pressure tested for leaks. 8.1.3 The certified LP Gas serviceman shall keep a written record of the inspection and all corrections made to the buried piping located in a public place. 8.1.4 The inspection records shall be available to be inspected on a regular basis by the Division. 8.2 Whenever the Division is required to complete more than two inspections to receive compliance on an LP Gas System, container, apparatus, appliance, appurtenance, tank or tank trailer, or any pertinent equipment for the storage, transportation or dispensation of LP Gas, the Division shall charge to the owner for each additional inspection, the re-inspection fee as stated in R710-6-6.1(e). 8.3 All LP Gas containers of more than 5000 water gallons shall be inspected at least biannually for compliance with the adopted statute and rules. The following containers are exempt from this requirement: 8.3.1 Those excluded from the act in UCA, Section 53-7-303. 8.3.2 Containers under federal control. 8.3.3 Containers under the control of the U.S. Department of Transportation and used for transportation of LP Gas. 8.3.4 Containers located at private residences. 8.4 Those using self-serve key or card services shall be trained in safe filling practices by the licensed dealer providing the services. A letter shall be sent to the Division by the licensed dealer stating that those using the self-serve key or card service have been trained. 8.5 IFC Amendments: 8.5.1 IFC, Section 3801.2 Permits. On line 2 after the word "105.7" add "and the adopted LPG rules". 8.5.2 IFC, Section 3803.1 - General. After the word "Code" on line 2 insert ",NFPA 54. 8.5.3 IFC, Section 3809.12 Location of storage outside of buildings. On line three replace the number "20" with the number "10". 8.6 NFPA, Standard 58 Amendments: 8.6.1 NFPA, Standard 58, Section [ 8.6.2 NFPA, Standard 58, Section [ 8.6.3 NFPA, Standard 58, Section [ 8.6.4 NFPA, Standard 58, Section [ 8.6.5 NFPA Standard 58, Sections [ Type K copper tubing without joints below grade may be used in exterior LP Gas piping systems only. 8.6.6 NFPA, Standard 58, Section [ 8.6.6.1 Constructed of steel not less than four inches in diameter and filled with concrete. 8.6.6.2 Set with spacing not more than four feet apart. 8.6.6.3 Buried three feet in the ground in concrete not less than 15 inches in diameter. 8.6.6.4 Set with the tops of the posts not less than three feet above the ground. 8.6.7 NFPA, Standard 58, Section [
KEY: liquefied petroleum gas [ Notice of Continuation July 5, 2001 53-7-305
|
|
ADDITIONAL INFORMATION |
|
|
PLEASE NOTE:
|
|
|
For questions regarding the content or application of this rule, please contact Brent Halladay at the above address, by phone at 801-284-6352, by FAX at 801-284-6351, or by Internet E-mail at bhallada@utah.gov For questions about the rulemaking process, please contact the Division of Administrative Rules (801-538-3764). Please Note: The Division of Administrative Rules is NOT able to answer questions about the content or application of these administrative rules. |
|