|
|
DAR File No. 28420 |
| This filing was published in the 01/01/2006, issue, Vol. 2006, No. 1, of the Utah State Bulletin. |
| [ 01/01/2006 Bulletin Table of Contents / Bulletin Page ] |
|
Environmental Quality, Drinking Water R309-540-6 Hydropneumatic Systems
|
NOTICE OF PROPOSED RULE |
|
DAR File No.: 28420
|
RULE ANALYSIS |
Purpose of the rule or reason for the change: |
|
The reason for the change is to change wording to refer to minimum water pressure described in Section R309-105-9. (DAR NOTE: The proposed amendment to Section R309-105-9 is under DAR No. 28416 in this issue.)
|
Summary of the rule or change: |
|
The change makes reference to Section R309-105-9 so that minimum pressures associated with existing systems will not be confused with minimum pressures required for new Public Water Systems designed and constructed after March 1, 2006.
|
State statutory or constitutional authorization for this rule: |
|
Section 19-4-104
|
Anticipated cost or savings to: |
the state budget: |
|
None--Since this amendment only clarifies this portion of rule and the additional water pressure requirements for new Public Water Systems, it will not require additional personnel or other funds from the state budget.
|
local governments: |
|
Little to None--Most, if not all, well functioning Public Water Systems operated by local government currently meet or exceed the current minimum water pressure minimums, as well as the proposed additional minimums. The design of new Public Water Systems will only require initial planning concerning storage location and distribution pipeline sizing which should not add significant cost or time.
|
other persons: |
|
Little to None--Most engineering companies currently look to typical textbook design standards, as well as standards of other agencies such as the American Water Works Association (AWWA), the American Society of Civil Engineers (ASCE), and other nearby states when designing Public Water Systems so there should not be any additional cost or time involved.
|
Compliance costs for affected persons: |
|
New Public Water Systems designed and constructed after March 1, 2006, should not see any costs over and above that if their system were designed with the typical capacity for anticipated growth and expansion. Some increased cost may be expected if storage tank location for adequate pressure requires additional length of transmission line.
|
Comments by the department head on the fiscal impact the rule may have on businesses: |
|
The department agrees that the proposed changes to this rule will have little to no detrimental impact on existing water systems nor on new public water systems. Dianne R. Nielson, Executive Director
|
The full text of this rule may be inspected, during regular business hours, at the Division of Administrative Rules, or at: |
|
Environmental Quality Drinking Water 150 N 1950 W SALT LAKE CITY UT 84116-3085
|
Direct questions regarding this rule to: |
|
Bill Birkes at the above address, by phone at 801-536-4201, by FAX at 801-536-4211, or by Internet E-mail at bbirkes@utah.gov
|
Interested persons may present their views on this rule by submitting written comments to the address above no later than 5:00 p.m. on: |
|
01/31/2006
|
This rule may become effective on: |
|
02/01/2006
|
Authorized by: |
|
Kevin Brown, Director
|
RULE TEXT |
|
R309. Environmental Quality, Drinking Water. R309-540. Facility Design and Operation: Pump Stations. R309-540-6. Hydropneumatic Systems. (1) General. Hydropneumatic systems shall comply with all appropriate sections of R309-540-5. Unpressurized ground level or elevated storage, designed in accordance with R309-545, shall be provided in addition to the diaphragm or air tanks. Diaphragm or air pressure tank storage shall not be considered for fire protection purposes or effective system storage. (2) Location. If diaphragm or air tanks and appurtenances are located below ground, adequate provisions for drainage, ventilation, maintenance, and flood protection shall be made and the electrical controls shall be located above grade so as to be protected from flooding as required by R309-540-5(6)(e). Any discharge piping from combination air release/vacuum relief valves(air/vac's) or pressure relief valves located in below ground chambers shall comply with all the pertinent requirements of R309-550-6(6). (3) Operating Pressures. The
system shall be designed to provide [ (4) Piping. In addition to the bypass required by R309-540-5(4)(iv) on the pumps, the diaphragm or air tanks shall have sufficient bypass piping to permit operation of the hydropneumatic system while one or more of the tanks are being repaired or painted. (5) Pumps. At least two pumping units shall be provided. With any pump out of service the remaining pump or pumps shall be capable of providing the peak instantaneous demand of the system as described in R309-510-9(2), while recharging the pressure tank at 115 percent of the upper pressure setting. Pump cycling shall not exceed 15 starts per hour, with a maximum of ten starts per hour preferred. (6) Pressure Tanks. (a) Pressure tanks shall meet the requirement of state and local laws and regulations for the manufacture and installation of unfired pressure vessels. Interior coatings or diaphragms used in pressure tanks that will come into contact with the drinking water shall comply with ANSI/NSF Standard 61. Non diaphragm pressure tanks shall have an access manhole, a drain, control equipment consisting of pressure gauge, water sight glass, automatic or manual air blow-off, means for adding air, and pressure operated start-stop controls for the pumps. (b) The minimum volume of the pressure tank or combination of tanks shall be greater than or equal to the sum of S and the value of CX divided by 4W. where the following values are used in the equation above: C = minutes per operating cycle, four minutes to meet the requirements of R309-540-6(5) above or preferably six minutes, and is equal to pump ON time plus pump OFF time. X = output capacity rating of the pump(s) at the high pressure condition in the tank(s), in gpm. W = percent of volume withdrawn during a given drop in tank pressure: specifically, between Ph and Pl. W = 100(Ph- Pl)/Ph where Ph = high pressure in tank in psia (high absolute pressure) and Pl = low pressure in tank is psia (low absolute pressure). Values of W range typically from 0.26 to 0.31 for pressure differentials of 15 to 30 psi and high system pressures of 45 to 85 psi at elevations of approximately 5,000 feet. S = water seal volume in gallons, the volume of inactive water remaining in tank at low pressure condition. (7) Air Volume. The method of adjusting the air volume shall be acceptable to the Executive Secretary. Air delivered by compressors to the pressure tank shall be adequately filtered, oil free, and be of adequate volume. Any intake shall be screened and draw clean air from a point at least 10 feet above the ground or other source of possible contamination, unless the air is filtered by an apparatus approved by the Executive Secretary. Discharge piping from air relief valves shall be designed and installed with screens to eliminate the possibility of contamination from this source. (8) Water Seal. For air pressure tanks without an internal diaphragm the volume of water remaining in a air pressure tank at the lower pressure setting shall be sufficient to provide an adequate water seal at the outlet to prevent the leakage of air. The following water seal depths shall be considered as minimum requirements. (a) Horizontal outlets shall maintain sufficient depth, as measured from the centerline of the horizontal outlet pipe, such that the depth is greater than or equal to the sum of d and twice the value v2 divided by 2G. (b) Vertical outlets, if unbaffled, the depth shall be the same as in (a) except measured from the pipe outlet; if baffled, the depth shall be greater than or equal to the value v2 divided by 2G. where the following values are used in the equations above: v = the axial velocity in the pipe outlet for the peak instantaneous demand flow rate of the system. d = the diameter of the outlet pipe in ft. G = the gravitational constant of 32.2 ft/sec/sec. (9) Standby Power Supply. Where a hydropneumatic system is intended to serve a public water system, categorized as a community water system as defined in R309-110, a standby source of power shall be provided.
KEY: drinking water, pumps, hydropneumatic systems, individual home booster pumps [ Notice of Continuation September 16, 2002 19-4-104
|
ADDITIONAL INFORMATION |
|
PLEASE NOTE:
|
|
For questions regarding the content or application of this rule, please contact Bill Birkes at the above address, by phone at 801-536-4201, by FAX at 801-536-4211, or by Internet E-mail at bbirkes@utah.gov For questions about the rulemaking process, please contact the Division of Administrative Rules (801-538-3764). Please Note: The Division of Administrative Rules is NOT able to answer questions about the content or application of these administrative rules. |
| [ 01/01/2006 Bulletin Table of Contents / Bulletin Page ] |
| Last modified: 12/28/2005 2:39 PM |